Nextiva S2800e Series User Guide
Verint Video Intelligence Solutions 27
to use the Nextiva IntelliFlow rules-based engine to create scenarios and responses based
on the state of these Nextiva signals; the type of event to select when creating a scenario is
Digital Input Pin. For more information, refer to the “IntelliFlow” chapter in the Nextiva
Administrator Guide.
To connect the alarm and relay wires to the interface board:
1. Strip approximately 1 inch (25 mm) of the outer jacket of each cable that will go in a
terminal block.
2. Strip approximately 0.25 inches (6 mm) of insulation off each individual wire on each
cable.
3. Connect the local input alarms:
a. Insert each alarm wire into the TB2 terminal block using the following wiring
information:
Under normal conditions, the alarm cable should be 22 AWG for a distance of
1000 feet (305 m).
b. Tighten the screws on the terminal block.
c. Install the terminal block on the interface board at the TB2 location.
d. Connect the other end of the alarm cable at the proper location.
4. Connect the local relay to the Nextiva alarm input:
a. Connect the relay wires between the TB4 terminal block and the Verint terminal
block using the following wiring information:
Pin Number Pin Label Signal Pin Number Pin Label Signal
TB2/1 ALM 1 Alarm input 1 TB2/5 ALM 3 Alarm input 3
TB2/2 GND Ground TB2/6 GND Ground
TB2/3 ALM 2 Alarm input 2 TB2/7 ALM 4 Alarm input 4
TB2/4 GND Ground TB2/8 GND Ground
Main Interface Board Verint Board
Pin Number Pin Label Signal
TB4/1 RELAY C Relay common Ground
TB4/2 RELAY NO Relay normally open Alarm input
TB4/3 RELAY NC Relay normally closed Not connected